UPS (NUT)
Plugin: go.d.plugin Module: upsd
Overview
This collector monitors Uninterruptible Power Supplies by polling the UPS daemon using the NUT network protocol.
This collector is supported on all platforms.
This collector supports collecting metrics from multiple instances of this integration, including remote instances.
Default Behavior
Auto-Detection
This integration doesn't support auto-detection.
Limits
The default configuration for this integration does not impose any limits on data collection.
Performance Impact
The default configuration for this integration is not expected to impose a significant performance impact on the system.
Metrics
Metrics grouped by scope.
The scope defines the instance that the metric belongs to. An instance is uniquely identified by a set of labels.
Per ups
These metrics refer to the UPS unit.
Labels:
Label | Description |
---|---|
ups_name | UPS name. |
battery_type | Battery type (chemistry). "battery.type" variable value. |
device_model | Device model. "device.mode" variable value. |
device_serial | Device serial number. "device.serial" variable value. |
device_manufacturer | Device manufacturer. "device.mfr" variable value. |
device_type | Device type (ups, pdu, scd, psu, ats). "device.type" variable value. |
Metrics:
Metric | Dimensions | Unit |
---|---|---|
upsd.ups_load | load | percentage |
upsd.ups_load_usage | load_usage | Watts |
upsd.ups_status | on_line, on_battery, low_battery, high_battery, replace_battery, charging, discharging, bypass, calibration, offline, overloaded, trim_input_voltage, boost_input_voltage, forced_shutdown, other | status |
upsd.ups_temperature | temperature | Celsius |
upsd.ups_battery_charge | charge | percentage |
upsd.ups_battery_estimated_runtime | runtime | seconds |
upsd.ups_battery_voltage | voltage | Volts |
upsd.ups_battery_voltage_nominal | nominal_voltage | Volts |
upsd.ups_input_voltage | voltage | Volts |
upsd.ups_input_voltage_nominal | nominal_voltage | Volts |
upsd.ups_input_current | current | Ampere |
upsd.ups_input_current_nominal | nominal_current | Ampere |
upsd.ups_input_frequency | frequency | Hz |
upsd.ups_input_frequency_nominal | nominal_frequency | Hz |
upsd.ups_output_voltage | voltage | Volts |
upsd.ups_output_voltage_nominal | nominal_voltage | Volts |
upsd.ups_output_current | current | Ampere |
upsd.ups_output_current_nominal | nominal_current | Ampere |
upsd.ups_output_frequency | frequency | Hz |
upsd.ups_output_frequency_nominal | nominal_frequency | Hz |
Alerts
The following alerts are available:
Alert name | On metric | Description |
---|---|---|
upsd_10min_ups_load | upsd.ups_load | UPS ${label:ups_name} average load over the last 10 minutes |
upsd_ups_battery_charge | upsd.ups_battery_charge | UPS ${label:ups_name} average battery charge over the last minute |
upsd_ups_last_collected_secs | upsd.ups_load | UPS ${label:ups_name} number of seconds since the last successful data collection |
Setup
Prerequisites
No action required.
Configuration
File
The configuration file name for this integration is go.d/upsd.conf
.
You can edit the configuration file using the edit-config
script from the
Netdata config directory.
cd /etc/netdata 2>/dev/null || cd /opt/netdata/etc/netdata
sudo ./edit-config go.d/upsd.conf
Options
The following options can be defined globally: update_every, autodetection_retry.
Config options
Name | Description | Default | Required |
---|---|---|---|
update_every | Data collection frequency. | 1 | no |
autodetection_retry | Recheck interval in seconds. Zero means no recheck will be scheduled. | 0 | no |
address | UPS daemon address in IP:PORT format. | 127.0.0.1:3493 | yes |
timeout | Connection/read/write timeout in seconds. The timeout includes name resolution, if required. | 2 | no |
Examples
Basic
A basic example configuration.
Config
jobs:
- name: local
address: 127.0.0.1:3493
Multi-instance
Note: When you define multiple jobs, their names must be unique.
Collecting metrics from local and remote instances.
Config
jobs:
- name: local
address: 127.0.0.1:3493
- name: remote
address: 203.0.113.0:3493
Troubleshooting
Debug Mode
To troubleshoot issues with the upsd
collector, run the go.d.plugin
with the debug option enabled. The output
should give you clues as to why the collector isn't working.
Navigate to the
plugins.d
directory, usually at/usr/libexec/netdata/plugins.d/
. If that's not the case on your system, opennetdata.conf
and look for theplugins
setting under[directories]
.cd /usr/libexec/netdata/plugins.d/
Switch to the
netdata
user.sudo -u netdata -s
Run the
go.d.plugin
to debug the collector:./go.d.plugin -d -m upsd
Do you have any feedback for this page? If so, you can open a new issue on our netdata/learn repository.